Edition: 02/2003
Magnetic Hydraulic Circuit Breaker W6 / W9
Electrical data
Calibration will hold 100% of rated current
may trip at 101...124% of rated load (134% for AC/DC units).
must trip at 125% of rated load and above (135% for AC/DC units)
Endurance 10x103on/off cycles - 6000 at rated load, 4000 without load
tested at 6 cycles/min, 1 s on and 9 s off at 25°C
Dielectric strength 50/60 Hz: 1500 Vrms
DC: 1100 Vdc
Insulation resistance 100x106Ohm
Features
·UL, CSA and VDE approved
·Ratings to 50 A
·Heavy duty stud connections
·Several delay curve options
·Trip free operation
·tested to EN 60934
U C V
Technical data of approved types on request
F0216-A
Typical resistance and impedance
Current rating DC resistance 50/60 Hz Impedance
Ac c
0.2 90 90
1.0 1.2 1.2
2.0 0.28 0.28
5.0 0.04 0.04
10.0 0.013 0.013
20.0 0.004 0.005
30.0 0.0027 0.004
40.0 0.002 0.002
50.0 0.0015 0.0015
Data for
ambient temperature +25°C
Approval and ratings
W6 series
Max Frequency Phase Current Interruption
Voltage Rating Capacity
V Hz A A
65 DC - 0.2...50 2000
250 50/60 1 0.2...30 5000
250 50/60 1 31...50 2000
415/240 50/60 3 0.2...30 5000
Approval and ratings
W9 series
Max Frequency Phase Current Interruption
Voltage Rating Capacity
V Hz A A
65 DC - 0.2...50 2000
250 50/60 1 0.2...30 5000
250 50/60 1 31...50 2000
415/240 50/60 3 0.2...30 5000