Product data sheet
Characteristics
RE22R1MLMR
Asym. Flashing Timing Relay - 0.05s…300h -
24…240V AC/DC - 1C/O
Main
Range of product Zelio Time
Product or component type Modular timing relay
Discrete output type Relay
Device short name RE22
Nominal output current 8A
Complementary
Contacts type and composition 1 C/O timed contact, cadmium free
Time delay type Li
Lit
L
Lt
Time delay range 0.05...1 s
30...300 min
30...300 h
30...300 s
3...30 h
0.3...3 s
3...30 min
3...30 s
10...100 s
1...10 s
Control type Rotary knob
Diagnostic button
Potentiometer external
[Us] rated supply voltage 24...240 V AC/DC 50/60 Hz
Release input voltage <= 2.4 V
Voltage range 0.85...1.1 Us
Supply frequency 50...60 Hz +/- 5 %
Connections - terminals Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
8/11/2020
1
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Tightening torque 0.6…1N.m conforming to IEC 60947-1
Housing material Self-extinguishing
Repeat accuracy +/- 0.5 % conforming to IEC 61812-1
Temperature drift +/- 0.05 %/°C
Voltage drift +/- 0.2 %/V
Setting accuracy of time delay +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
Control signal pulse width 100ms with load in parallel
30ms
Insulation resistance 100 MOhm at 500V DC conforming to IEC 60664-1
Recovery time 120ms on de-energisation
Immunity to microbreaks 10ms
Power consumption in VA 3VA at 240 V AC
Power consumption in W 1.5W at 240 V DC
Switching capacity in VA 2000VA
Minimum switching current 10mA at 5 V DC
Maximum switching current 8A
Maximum switching voltage 250V AC
Electrical durability 100000cycles, 8A at 250 V, AC-1
100000cycles, 2A at 24 V, DC-1
Mechanical durability 10000000cycles
Rated impulse withstand voltage 5kV for 1.2…50µs conforming to IEC 60664-1
Power on delay 100ms
Creepage distance 4 kV/3 conforming to IEC 60664-1
Overvoltage category III conforming to IEC 60664-1
Safety reliability data MTTFd = 194 years
B10d = 180000
Mounting position Any position
Mounting support 35 mm DIN rail conforming to EN/IEC 60715
Status LED LED backlight green (steady) for dial pointer indication
LED yellow (steady) for output relay energised
LED yellow (fast flashing) for timing in progress and output relay de-energised
LED yellow (slow flashing) for timing in progress and output relay energised
Width 22.5mm
Net weight 0.1kg
Environment
Dielectric strength 2.5kV for 1 mA/1 minute at 50 Hz between relay output and power supply with basic insulation
conforming to IEC 61812-1
Standards IEC 61812-1
UL 508
Directives 2004/108/EC - electromagnetic compatibility
2006/95/EC - low voltage directive
Product certifications EAC
UL
GL
China RoHS
CSA
RCM
CCC
CE
Ambient air temperature for operation -20…60°C
Ambient air temperature for storage -40…70°C
IP degree of protection IP40 housing: conforming to IEC 60529
IP50 front face: conforming to IEC 60529
IP20 terminals: conforming to IEC 60529
Pollution degree 3 conforming to IEC 60664-1
2
Vibration resistance 20 m/s² (f= 10…150Hz) conforming to IEC 60068-2-6
Shock resistance 15 gn not operating for 11ms conforming to IEC 60068-2-27
5 gn in operation for 11ms conforming to IEC 60068-2-27
Relative humidity 95% at 25…55°C
Electromagnetic compatibility Fast transients immunity test - test level: 1 kV level 3 (capacitive connecting clip) conforming to IEC
61000-4-4
Surge immunity test - test level: 1 kV level 3 (differential mode) conforming to IEC 61000-4-5
Surge immunity test - test level: 2 kV level 3 (common mode) conforming to IEC 61000-4-5
Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2
Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 (80 MHz...1
GHz) conforming to IEC 61000-4-3
Conducted RF disturbances - test level: 10 V level 3 (0.15...80 MHz) conforming to IEC 61000-4-6
Fast transient bursts - test level: 2 kV level 3 (direct contact) conforming to IEC 61000-4-4
Immunity to microbreaks and voltage drops - test level: 30 % (500 ms) conforming to IEC 61000-4-11
Immunity to microbreaks and voltage drops - test level: 100 % (20 ms) conforming to IEC 61000-4-11
Packing Units
Package 1 Weight 0.090kg
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation REACh Declaration
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Environmental Disclosure Product Environmental Profile
Circularity Profile End of Life Information
3
Product data sheet
Dimensions Drawings
RE22R1MLMR
Dimensions
4
Product data sheet
Connections and Schema
RE22R1MLMR
Wiring Diagram
5
Product data sheet
Technical Description
RE22R1MLMR
Function L: Asymmetrical Flashing Relay (Starting Pulse Off)
Description
On energisation of power supply, output(s) R starts at its/their initial state for timing duration Tr then change(s) to output(s) R close(s) for the
another timing duration Ta.This cycle is repeated indefintely until power supply removal.
Function: 1 Output
6
Product data sheet
Technical Description
RE22R1MLMR
Function Li: Asymmetrical Flashing Relay (Starting Pulse On)
Description
On energisation of power supply, output(s) R starts at output(s) R close(s) for timing duration Ta then change(s) to its/their initial state for timing
duration Tr.This cycle is repeated indefintely until power supply removal.Specially for RE22R1MLMR, this Li function can only be initiated by
energizing X2 permanently.
Function: 1 Output with Function Selection
Function: 1 Output
7
Product data sheet
Technical Description
RE22R1MLMR
Function Lt: Asymmetrical Flashing Relay (Starting Pulse Off) & with Pause / Summation Control
Description
On energisation of power supply, output(s) R starts at its/their initial state for timing duration Tr and the timing can be interrupted / paused each
time X1 energizes.When the cumulative total of time periods elapsed reaches the pre-set value Tr, then changes to output(s) R close(s).The
output(s) R close state will remain for the same timing duration Ta and the timing can be interrupted / paused each time X1 energizes. When
the cumulative total of time periods elapsed reaches the pre-set value Ta, the output(s) R revert(s) to its/their initial state.This cycle is repeated
indefinitely until power supply removal.
Function: 1 Output
T = t1 + t2 +…
T = t'1 + t'2 +…
8
Product data sheet
Technical Description
RE22R1MLMR
Function Lit: Asymmetrical Flashing Relay (Starting Pulse On) & Pause / Summation Control
Description
On energisation of power supply, output(s) R starts at output(s) R close(s) for timing duration Ta and the timing can be interrupted / paused each
time X1 energizes.When the cumulative total of time periods elapsed reaches the pre-set value Ta, the output(s) R revert(s) to its/their initial
state.The output(s) R at intial state will remain for timing duration Tr the timing can be interrupted / paused each time X1 energizes. When the
cumulative total of time periods elapsed reaches the pre-set value Tr, then changes to output(s) R close(s) This cycle is repeated indefintely until
power supply removal.Specially for RE22R1MLMR, this Li function can only be initiated by energizing X2 permanently
Function: 1 Output with Function Selection
T = t1 + t2 +…
T = t'1 + t'2 +…
Legend
Relay de-energised
Relay energised
Output open
Output closed
U - Supply
R1 - Timed output
Ta - Adjustable On-delay
Tr - Adjustable Off-delay
X1 - Pause / Summation control
X2 - Function Selection
9