Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Tightening torque 0.6…1N.m conforming to IEC 60947-1
Housing material Self-extinguishing
Repeat accuracy +/- 0.5 % conforming to IEC 61812-1
Temperature drift +/- 0.05 %/°C
Voltage drift +/- 0.2 %/V
Setting accuracy of time delay +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
Control signal pulse width 100ms with load in parallel
30ms
Insulation resistance 100 MOhm at 500V DC conforming to IEC 60664-1
Recovery time 120ms on de-energisation
Immunity to microbreaks 10ms
Power consumption in VA 3VA at 240 V AC
Power consumption in W 1.5W at 240 V DC
Switching capacity in VA 2000VA
Minimum switching current 10mA at 5 V DC
Maximum switching current 8A
Maximum switching voltage 250V AC
Electrical durability 100000cycles, 8A at 250 V, AC-1
100000cycles, 2A at 24 V, DC-1
Mechanical durability 10000000cycles
Rated impulse withstand voltage 5kV for 1.2…50µs conforming to IEC 60664-1
Power on delay 100ms
Creepage distance 4 kV/3 conforming to IEC 60664-1
Overvoltage category III conforming to IEC 60664-1
Safety reliability data MTTFd = 194 years
B10d = 180000
Mounting position Any position
Mounting support 35 mm DIN rail conforming to EN/IEC 60715
Status LED LED backlight green (steady) for dial pointer indication
LED yellow (steady) for output relay energised
LED yellow (fast flashing) for timing in progress and output relay de-energised
LED yellow (slow flashing) for timing in progress and output relay energised
Width 22.5mm
Net weight 0.1kg
Environment
Dielectric strength 2.5kV for 1 mA/1 minute at 50 Hz between relay output and power supply with basic insulation
conforming to IEC 61812-1
Standards IEC 61812-1
UL 508
Directives 2004/108/EC - electromagnetic compatibility
2006/95/EC - low voltage directive
Product certifications EAC
UL
GL
China RoHS
CSA
RCM
CCC
CE
Ambient air temperature for operation -20…60°C
Ambient air temperature for storage -40…70°C
IP degree of protection IP40 housing: conforming to IEC 60529
IP50 front face: conforming to IEC 60529
IP20 terminals: conforming to IEC 60529
Pollution degree 3 conforming to IEC 60664-1
2