1601-800-526-2324 • www.us.tdk-lambda.com/lp/ Disclaimer: us.tdk-lambda.com/lp/legal.htm
ZUP Series
Features
Constant Voltage / Constant Current
Last Setting Memory
Digital Meters
Built-in RS232 & RS485 Interface
Bench or Rack Mount
Embedded Microprocessor Controller
Voltage up to 120V, Current up to 132A
Zero up programmable power supplies
Notes: (1) Recovery to within +/-50mV after load change of 50-100% (2) Over 8 hour period following 30 minute warm up time
(3) 25°C ambient (cold start)
Model ZUP6 ZUP10 ZUP20 ZUP36 ZUP60 ZUP80 ZUP120
Load Regulation - 2mV + 0.005% over 0 - 100% load change
Line Regulation - 1mV + 0.005% over 85 - 132 or 170 - 265VAC line change
Recovery Time (1) ms 1ms 0.5ms 0.2ms
Temperature Coef cient - 30ppm/°C following 30 minute warm up
Temperature Drift(2) - 0.01% + 2mV change in output
Up programming response time ms 50 - 60ms 80ms 120ms
Down prog. resp. time (CV) ms 50ms (70ms ZUP60-14)
Down prog. resp. time (CV) ms 250ms 350ms 400ms 500ms 750ms 600ms 800ms
Load Regulation - 0.01% + 5mA on 200W and 400W models, 0.07% + 10mA on 800W models
Line Regulation - 0.01% + 2mA on 200W and 400W models, 0.01% + 5mA on 800W models
Temperature Coef cient - 100ppm/°C from rated current after 30 minute warm up time
Temperature Drift(2) - 0.02% + 5mA, 200W and 400W models, 0.05% + 10mA 800W models
Prog Voltage resolution - Better than 0.028% of rated voltage
Prog Voltage accuracy mV .02%+5mV .02%+8mV .02%+12mV .02%+20mV .02%+35mV .02%+50mV .02%+70mV
Prog Current resolution - Better than 0.03% of rated output current
Prog Current accuracy - 0.4% + 40mA
Overvoltage Shutdown V 0 - 7.5 0 - 13 0 - 24 0 - 40 0 - 66 0 - 88 0 - 132
Thermal Protection - Over temperature protected
Display - Voltage - 3 digits (6, 20, 36, 60, 80V models), 3.5 digits (10, 120V models). Accuracy 0.2% ± 2 digits
Display - Current - 3 digits, (3.5 digits 132A model). Accuracy 0.5% ± 3 digits
Display - Status - CV / CC, Alarm, Foldback, Local/Remote, On/Off
Remote On/Off - TTL signal or dry contact relay
Output Good - Open Collector
Voltage & Current Programming - By either Voltage (0-4V) or Resistance (0-4k)
Remote Sense - Up to 0.5V compensation per output cable
Communication Interface - RS232 & RS485 standard, IEEE488 optional
Series & Parallel Operation - Series: Up to two units; Parallel: Up to ve units in master-slave con guration
AC Input Voltage range VAC 85-265VAC (47-63Hz)
Inrush Current (100/200VAC)(3) A 15/30A, 200W models, 15A, 400W models, 30A, 800W models
Hold Up Time (Typ) at 100VAC ms 20
Power Factor Correction - Complies with EN61000-3 Class A (0.99 typ)
Temperature Range - Operating: 0 - 50°C; Storage: -20 to +70°C
Humidity (non condensing) - Operating: 30 - 90% RH, Storage 10 - 95%RH
Cooling - Internal fan
Withstand Voltage - Input to Ground 2kVAC, Input to Output 3kVAC, Output to Ground 500VAC for 1 min.
Isolation Resistance - >100M at 25°C & 70%RH
Vibration & Shock (non-op.) - Vibration:10-55Hz(1 min.) 2G constant X, Y, Z, when correctly mounted; Shock: <20G
Safety Agency Approvals - UL3111-1, EN61010-1, CE Mark
Conducted & Radiated EMI - EN55022-B conducted, A radiated, FCC Class B conducted, A radiated, VCCI-2 conducted, -1 radiated
Warranty yrs Three Years
Speci cations
Key Market Segments & Applications
1611-800-526-2324 • www.us.tdk-lambda.com/lp/ Revision A9: Jun 2017
ZUP Series
For Additional Information, please visit
us.tdk-lambda.com/lp/products/zup.htm
Outline Drawing 200/400W
Outline Drawing 800W
Voltage Current Ripple Noise Ripple Ef ciency
Adjust Adjust Max 5Hz-1MHz 20MHz BW 5Hz-1MHz % Weight
Model Range Range Power mV mV mA (100/200VAC) kg
ZUP6-33/U 0-6 0-33 198 5 50 50 69 / 72 2.9
ZUP6-66/U 0-6 0-66 396 5 50 100 74 / 77 3.2
ZUP6-132/U 0-6 0-132 792 8 100 200 74 / 77 5.8
ZUP10-20/U 0-10 0-20 200 5 50 25 73 / 77 2.9
ZUP10-40/U 0-10 0-40 400 5 50 50 79 / 82 3.2
ZUP10-80/U 0-10 0-80 800 8 90 100 77 / 81 5.8
ZUP20-10/U 0-20 0-10 200 5 50 15 74 / 78 2.9
ZUP20-20/U 0-20 0-20 400 5 50 30 79 / 83 3.2
ZUP20-40/U 0-20 0-40 800 5 80 60 79 / 82 5.8
ZUP36-6/U 0-36 0-6 216 5 50 7.5 76 / 80 2.9
ZUP36-12/U 0-36 0-12 432 5 50 15 80 / 84 3.2
ZUP36-24/U 0-36 0-24 864 5 70 30 80 / 84 5.8
ZUP60-3.5/U 0-60 0-3.5 210 5 50 5 75 / 79 2.9
ZUP60-7/U 0-60 0-7 420 5 50 10 80 / 84 3.2
ZUP60-14/U 0-60 0-14 840 5 60 20 80 / 84 5.8
ZUP80-2.5/U 0-80 0-2.5 200 30 80 5 77 / 82 2.9
ZUP80-5/U 0-80 0-5 400 30 80 10 83 / 87 3.2
ZUP120-1.8/U 0-120 0-1.8 216 30 80 5 77 / 82 2.9
ZUP120-3.6/U 0-120 0-3.6 432 30 80 10 83 / 87 3.2
Model Selector
Option Model Suf x Part Number
Front panel terminals (20A max)5 /L4 ZUP200/400/L4
Front panel terminals (20A max)6 /L4 ZUP800/L4
IEC320 cable USA plug /U ZUP/U
Serial link cable RJ-45 /W ZUP/W
Dual Unit Assembly ZUP/NL200
(accepts 200W or 400W models)
19” 3U rack (accepts up to 6 200/400W models) ZUP/NL100
Blanking panels for NL100 (19 in. rack) ZUP/NL101
RS232 Communications Cable DB-9 ZUP/NC401
RS232 Communications Cable DB-25 ZUP/NC403
RS485 Communications Cable DB-9 ZUP/NC402
RS485 Communications Cable DB-25 ZUP/NC404
User Manual NL102
4 Not available with ZUP80 or ZUP120 models.
5 200W and 400W models
6
800W models
Options & Accessories
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
TDK-Lambda:
ZUP/E ZUP/U ZUP/W ZUP10-20 ZUP10-20/LU ZUP10-20/LUW ZUP10-20/U ZUP10-40 ZUP10-40/LU ZUP10-
40/LUW ZUP10-40/U ZUP10-80 ZUP10-80/U ZUP120-1.8 ZUP120-1.8/U ZUP120-3.6 ZUP120-3.6/U ZUP20-10
ZUP20-10/LU ZUP20-10/LUW ZUP20-10/U ZUP20-20 ZUP20-20/LU ZUP20-20/LUW ZUP20-40 ZUP20-40/U
ZUP36-12 ZUP36-12/LU ZUP36-24 ZUP36-24/U ZUP36-6/LU ZUP36-6/LUW ZUP60-14/LU ZUP60-3.5 ZUP60-
3.5/LUW ZUP60-3.5/U ZUP60-7 ZUP60-7/U ZUP6-132/U ZUP6-33 ZUP6-33/LU ZUP6-33/LUW ZUP6-66 ZUP6-
66/LUW ZUP6-66/U ZUP800/L ZUP80-2.5 ZUP80-2.5/U ZUP80-5 ZUP80-5/U ZUP60-3.5/LU ZUP60-7/LUW
ZUP6-33/U ZUP60-7/LU ZUP60-14/U ZUP6-66/LU ZUP36-12/U ZUP36-12/LUW ZUP60-14/LUW ZUP200/400/L
ZUP36-6/U ZUP6-132 ZUP36-6 ZUP20-20/U ZUP60-14 NL200 ZUP/NL200