480W Single Output Industrial DIN RAIL with PFC Function DRP-480 series Features : Built-in passive PFC function compliance to EN61000-3-2 High efficiency 89% and low dissipation Protections: Short circuit / Overload / Over voltage / Over temperature Cooling by free air convection Built-in constant current limiting circuit Can be installed on DIN rail TS-35/7.5 or 15 UL 508(industrial control equipment)approved EN61000-6-2(EN50082-2) industrial immunity level 100% full load burn-in test 3 years warranty Bauar t gepruft Sicherheit egel ma ge od o s be wac g SPECIFICATION MODEL OUTPUT DRP-480-24 DRP-480-48 DC VOLTAGE 24V 48V RATED CURRENT 20A 10A CURRENT RANGE 0 ~ 20A 0 ~ 10A RATED POWER 480W 480W RIPPLE & NOISE (max.) Note.2 120mVp-p 120mVp-p VOLTAGE ADJ. RANGE 24 ~ 28V VOLTAGE TOLERANCE Note.3 1.0% 48 ~ 53V 1.0% LINE REGULATION 0.5% 0.5% LOAD REGULATION 1.0% 1.0% SETUP, RISE TIME 1200ms, 40ms/230VAC at full load HOLD UP TIME (Typ.) 16ms/230VAC at full load VOLTAGE RANGE 180 ~ 264VAC FREQUENCY RANGE 47 ~ 63Hz NR 250 ~ 370VDC POWER FACTOR (Typ.) 0.7 EFFICIENCY (Typ.) 89% AC CURRENT (Typ.) INRUSH CURRENT (Typ.) 4A/230VAC COLD START 40A/230VAC ND INPUT www. tuv.com ID 2000000000 LEAKAGE CURRENT <3.5mA / 240VAC OVERLOAD 105 ~ 150% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed 54 ~ 60V 30 ~ 36V PROTECTION OVER VOLTAGE OVER TEMPERATURE WORKING TEMP. Protection type : Shut down o/p voltage, re-power on to recover 1005 (TSW : detect on heatsink of power switch) Protection type : Shut down o/p voltage, recovers automatically after temperature goes down -20 ~ +70 (Refer to "Derating Curve") WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION SAFETY STANDARDS 20 ~ 90% RH non-condensing SAFETY & WITHSTAND VOLTAGE ISOLATION RESISTANCE EMC (Note 4) EMC EMISSION I/P-O/P:3KVAC OTHERS 0.03%/ (0 ~ 50) Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 UL508, UL60950-1, TUV EN60950-1, EAC TP TC 004 approved I/P-FG:2.0KVAC O/P-FG:0.5KVAC I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25/ 70% RH Compliance to EN55032 (CISPR32) Class B, EN61000-3-2,-3, EAC TP TC 020 EMC IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 (EN50082-2), heavy industry level, criteria A, EAC TP TC 020 MTBF 180.9Khrs min. MIL-HDBK-217F (25) 227*125.2*100mm (W*H*D) 2.4Kg; 6pcs/15Kg/1.75CUFT DIMENSION PACKING NOTE -20 ~ +85, 10 ~ 95% RH 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. The ambient temperature derating of 3.5/1000m with fanless models and of 5/1000m with fan models for operating altitude higher than 2000m(6500ft). File Name:DRP-480-SPEC 2018-01-12 DRP-480 series 480W Single Output Industrial DIN RAIL with PFC Function Mechanical Specification Case No.930 227 125.2 100 Unit:mm TB1 3 2 1 TB2 LED 4 3 2 1 +V ADJ. Terminal Pin No. Assignment (TB1) ADMISSIBLE DIN-RAIL: TS35/7.5 OR TS35/15 NR 35 EMI FILTER RECTIFIERS & FILTER PASSIVE PFC Pin No. 1,2 3,4 POWER SWITCHING FG O.L.P. O.T.P. Assignment AC/L(DC+) AC/N(DC-) FG Terminal Pin No. Assignment (TB2) ND Block Diagram I/P Pin No. 1 2 3 Assignment DC OUTPUT +V DC OUTPUT -V fosc : 70KHz RECTIFIERS & FILTER +V -V DETECTION CIRCUIT CURRENT LIMIT PWM CONTROL Derating Curve O.V.P. Output Derating VS Input Voltage 100 100 90 80 80 70 LOAD (%) LOAD (%) 60 40 20 -20 0 10 20 30 40 50 AMBIENT TEMPERATURE () 60 70 (VERTICAL) 60 50 40 180 190 200 264 INPUT VOLTAGE (V) 60Hz File Name:DRP-480-SPEC 2018-01-12