Technical DataTechnical Data
Power quality that meets the standard:
All measurements comply with IEC61000-4-30
standards for correct evaluation of all measured
values including voltage, current, power, har-
monics, fl icker etc.
Quick and reliable confi guration: PDA wire-
less “front panel interface” provides the ability
to verify setup without a laptop along with a
window into what the instrument is recording,
even in awkward test locations.
Threshold-free setup: Apply thresholds after
data is collected with Fluke Power Analyze
Software so there is no need to worry about
missed information due to incorrect set-up.
Captures everything: Cross-channel and current
triggering capture every measurement, on every
channel, every time.
Capture every measurement, every event,
on every cycle, all the time with the Fluke
1750 Power Recorder. Outstanding accuracy
and resolution provide complete visibility into
your installation or distribution system.
Fluke 1750
Three-Phase Power Recorder
Never miss capturing a
disturbancewith the exclusive
threshold-free measurement
system, it’s automatic.
Intuitive PC software: Easily analyze data and
generate reports. Automated EN50160 reporting
and compliance.
Plug and play: Set up in minutes with self-
identifying current probes and single-lead voltage
connections.
No need to reconnect wires: Swap channels
internally with the wireless PDA or PC when
connections are not correct.
Measure every parameter: voltage and current
on three phases, neutral, and ground.
5 MHz, 8000 Vpk waveform capture: Get a
detailed picture of even the shortest events.
Quickly retrieve data: With included SD memory
card or via the 100BaseT high-speed Ethernet
connection.
2 Fluke Corporation Fluke 1750 Three-Phase Power Recorder
Applications
Long-term analysis: Uncover hard-to-fi nd or
intermittent issues; monitor critical equipment,
capturing power quality events to correlate with
equipment malfunction
Power quality surveys: Quantify power quality
throughout a facility, documenting results with
professional reports
Quality of service compliance: Validate incoming
power quality at the service entrance
Equipment Installation/Commissioning: Bench-
mark power system prior to install to insure quality
of service
Easy to use
The recorder automatically detects, scales, and
powers current probes without needing batteries.
Requiring only single-lead voltage connections
enables safe and quick setups. Once power is
applied the instrument automatically begins record-
ing and LEDs give you assurance that the recorder
is powered up and signals are within range – no
more uncertainty that data is being recorded. The
Fluke 1750 has an exclusive capture algorithm
which makes certain all events are captured with-
out the tedious setups and blind spots associated
with threshold driven equipment.
The PDA wirelessly interfaces with the recorder,
allowing quick setup and verifi cation with wave-
form displays, meter screens, and phasor diagrams.
The built-in wireless technology allows you to
control multiple instruments from a distance easily,
without the need for a laptop computer (laptops can
also be used when desired).
View measurements real-time with
wireless PDA interface.
Configurations are simple with wiring
diagrams to guide you.
No need to reconnect wires—swap channels
internally using the PDA interface.
3 Fluke Corporation Fluke 1750 Three-Phase Power Recorder
Comprehensive power system data
Every cycle on every channel is simultaneously
sampled providing complete analysis of power
quality, harmonics, power and energy. Cross-
channel current and voltage triggering captures
Powerful data management
Data is automatically stored on the internal fl ash
memory that can store records for over a month
without compression or overwriting. Data is
retrieved via one of two quick and easy options:
download the data onto the included SD memory
Events can be displayed against a variety of tolerance curves.
card without using your laptop, or transfer directly
to your computer via Ethernet, using TCP/IP protocol.
Voice, data, and picture annotations can be made
via the PDA to fl ag important points in the data
stream. Imagine being able to fl ag in your recorded
data when a transfer switch was operated, or load
changes were made.
Full FFT on each channel to the 50th harmonic.
Display multiple parameters simultaneously on one graph.
EN50160 report delivers an easy to read pass or fail chart
along with drill down data.
Full-featured power meter display for each channel and totals.
Thresholds for the EN50160 report are easily customized.
event data on all input channels simultaneously,
no matter which channel triggered the event. When
periodic analysis of the waveform may be needed,
the Snapshot mode captures waveforms at user-
defi ned intervals. Even dc signals can be recorded!
4 Fluke Corporation Fluke 1750 Three-Phase Power Recorder
IEC 61000-4-30 compliant measurement systems pro-
vide the confi dence that all parameters are measured
and calculated consistently with international standards.
Automated EN50160 compliance reporting for rapid Pass/
Fail testing.
Designed to help protect you and your equipment,
the Fluke 1750 Three-Phase Power Recorder and accesso-
ries are all certifi ed to meet the stringent safety standards
for use in 600 V CAT IV and 1000 V CAT III environ-
ments. They are the fi rst tools of their kind to carry the
CAT IV rating and, therefore, can be used for most power
connections and for all outlets in a low-voltage power
distribution system.
View data the way you want
The new Fluke Power Analyze software revolu-
tionizes your ability to analyze data. No need to
worry about thresholds—with Fluke Power Ana-
lyze, thresholds can be modifi ed after the data is
recorded! And the easy-to-use user interface will
display voltage as a phase-to-phase or phase-to-
neutral reading.
Apply thresholds to data after collection using a variety of
standard or customized templates.
Simplified report writer feature included in Fluke Power
Analyze.
All the latest power quality
standards are built-in
600 V CAT IV and
1000 V CAT III safety rating
5 Fluke Corporation Fluke 1750 Three-Phase Power Recorder
Optional Accessories
Fluke power quality current
transformers and fl exible current
probes are specially designed
to work seamlessly with Fluke
power monitors (1750 and 1650).
All clamp-on and fl exi-CT’s are
matched to take full advantage
of your instrument’s ability to
set scale factors for accurate
readings.
Cases
1750/CASE Transit Case
Rugged water tight transit case
with rollers
Miscellaneous
1750/MC
Additional SD Memory Card
for Fluke 1750
1750/ SEAT-L
Fluke Power Analyze –
Additional SEAT LICENSE
One additional license for
installation on one additional
PC
1750/SITE-L
Fluke Power Analyze -
Additional SITE LICENSE
Site license for installation on
unlimited PCs
4006 Security Cable
1.8 m (6 ft) looped lockable
steel cable for securing monitor
Model No. CT Type Current Range Accuracy
Frequency
Response Jaw Opening
3005-PR Clamp-On 0.01 A to 5 A 1 % RDG ± 0.5 % FS 5 kHz 2 cm (.78 in) dia.
3014-PR Clamp-On 0.1 A to 40 A 1 % RDG ± 0.1 % FS 5 kHz 2 cm (.78 in) dia.
3140R Clamp-On 2 A to 400 A 2 % RDG ± 0.04 A 20 kHz 3.2 cm (1.25 in) dia.
Model No. CT Type Current Range Accuracy
Frequency
Response Probe Length
3110-PR Flexi-CT 2 A to 100 A 1 % rdg ± 0.5 % FS 7 kHz 60 cm (24 in)
3210-PR Flexi-CT 20 A to 1000 A 1 % rdg ± 0.15 % FS 7 kHz 60 cm (24 in)
3310-PR Flexi-CT 100 A to 5000 A 1 % rdg ± 0.15 % FS 7 kHz 60 cm (24 in)
3312-PR Flexi-CT 100 A to 5000 A 1 % rdg ± 0.15 % FS 7 kHz 120 cm (48 in)
6 Fluke Corporation Fluke 1750 Three-Phase Power Recorder
Specifi cations for the System:
Recorder and Power Analyze Software
General
Power quality measurement standards
Conformance IEC 61999-1-4 Class 1, IEC 61000-4-30, IEEE519, IEEE1159, IEEE1459 and EN50160
Clock/calendar Leap years, 24-hour clock
Real-time clock accuracy Not more than ± 1 s/day
Internal memory capacity for data At least 2 GB
Maximum recording period At least 31 days
Measurement time control Automatic
Maximum number of events Limited only by the size of the internal memory
Power requirements 100 to 240 V rms ± 10 %, 47-63 Hz, 40 W
Operating time during interruptions
(internal UPS operation)
5 minutes per interruption, 60 minutes total operating time without recharging
Dimensions 215 mm x 310 mm x 35 mm (8.5 in x 12.2 in x 3.5 in)
Mass (weight) 6.3 kg (14 lb)
Input
Measurement types One Phase Plus Neutral, One Phase IT No Neutral, One Phase Split Phase, Three Phase Wye,
Three Phase Delta, Three Phase IT, Three Phase High Leg, Three Phase Open Leg, 2 Element Delta,
21/2 Element Wye
Input channels Voltage: 4 channels, ac/dc
Current: 5 channels
Voltage channels Input resistance: 2 MΩ
Input capacitance: < 20 pF
Current input characteristics 2 V rms = full scale, 1 MΩ Input Impedance for ferro CTs, low impedance for Flexi-CTs
Measuring method Simultaneous digital sampling of voltage and current. Digital PLL synchronized sampling, internal
frequency reference used during voltage drops.
Synchronization and sampling
PLL-synchronization source The PLL synchronizes to the A-N voltage for wye power types, and to the A-B voltage for delta
power types. All listed power types can be characterized as either wye or delta.
PLL lock range 42.5 to 69 Hz
Sampling frequency Voltage and current: 256 samples/cycle
Inter-harmonics per IEC 61000-4-7: 2560 points/10 cycles (50 Hz),
3072 points/12 cycles (60 Hz)
Transient Voltage: 5 MHz
A/D resolution Voltage and current: 24 bits
Transient voltage: 14 bits
Voltage and current measurements
Voltage measurement range AC voltage: 1000 V rms ± 10 % over range
DC voltage: ± 1000 V + 10 % over range
Voltage crest factor 3 or less
Current measurement range Depends on current probe used
Current crest factor 4 or less
Voltage and current measurement accuracy
RMS voltage
Measurement type True rms calculated continuously: every cycle, every 1/2 cycle, and
every 10 or 12 cycles at 50 or 60 Hz respectively, as required by IEC 61000-4-30.
Measurement uncertainty
AC: ± 0.2 % reading ± 0.1 % full scale, above 50 V rms
DC: ± 0.5 % reading ± 0.2 % full scale, above 50 V dc
RMS current
Measurement type True rms calculated continuously: every cycle, every 1/2 cycle, and
every 10 or 12 cycles at 50 or 60 Hz respectively, as required by standards
Measurement uncertainty Ferromagnetic Clamps: ± (0.1 % full scale + 0.2 % reading + current sensor accuracy),
valid for 5 % to 100 % of current sensor range
Flexible Current Probes: ± (0.1 % full scale + 0.5 % reading + current sensor accuracy),
valid for 5 % to 100 % of current sensor range
7 Fluke Corporation Fluke 1750 Three-Phase Power Recorder
Transient voltage (impulse)
Measurement type Waveshape sampling
Full scale 8000 V pk
Sample resolution 200 nS
Measurement uncertainty ± 5 % reading ± 20 V (test parameters: 1000 V dc, 1000 V rms, 100 kHz)
Dip (Sag) and Swell Measurements
Voltage swell (rms swell)
Measurement type True rms (one cycle calculation by overlapping each half cycle - voltage between lines is measured
for 3P3W lines and phase voltage is measured for 3P4W lines)
Displayed data Amplitude and duration of swell
Measurement uncertainty Same as rms voltage
Voltage dip (rms sag)
Measurement type True rms (one cycle calculation by overlapping each half cycle - voltage between lines is measured
for 3P3W lines and phase voltage is measured for 3P4W lines)
Displayed data Amplitude and duration of dip or interruption
Measurement uncertainty Same as rms voltage
Voltage dropout (interruption)
Measurement type Same as voltage dip
Power Measurements
Calculated per IEEE1459 for best performance when distortion is present
Measurement type True rms calculated continuously: every cycle, and every 10 or 12 cycles at 50 or 60 Hz respec-
tively, as required by standards
Measurement accuracy +/- (voltage uncertainty + current uncertainty + current probe uncertainty)
Frequency
Measurement range 42.5 to 69 Hz
Measurement source Same as PLL synchronization source
Measurement accuracy ± 10 mHz (10 to 110 % of range, with sine wave)
Power factor
Measurement range 0.000 to 1.000
Measurement accuracy ± 1 digit from the calculation of each measured value (±3 digits for total)
Displacement power factor
Measurement method Calculated from the phase difference between voltage fundamental and current fundamental
Measurement range - 1.000 (leading) to + 1.000 (lagging)
Measurement accuracy ± 0.5 % reading ± 2 % full scale ± 1 digit
Voltage unbalance and phase sequence
Measurement method Positive sequence voltage divided by negative sequence voltage, per IEC 61000-4-30
Harmonic voltage and current
Analysis window rectangular
Analysis order 1st to 50th order
Measurement accuracy Voltage / Current: 1st to 20th orders: ± 0.5 % reading ± 0.2 % full scale, 21st to 50th orders: ± 1 %
reading ± 0.3 % full scale (current sensor accuracy must be included for current and power)
Measurement method IEC 61000-4-7
Inter-harmonic voltage and current (intermediate harmonics)
Analysis window rectangular
Analysis orders 1.5 to 49.5th order
Measurement method IEC 61000-4-7
Voltage fl icker
Measurement method as per EN 61000-4-15:2003: 10 min (Pst), 2 h (Plt)
8 Fluke Corporation Fluke 1750 Three-Phase Power Recorder
External Interface Specifi cations
LAN interface
Connector RJ-45
Speed and type 10/100 Base-T, auto MDIX
Communications protocol TCP/IP over Ethernet
Wireless controller interface
Connection wireless (2.4 GHz radio)
Speed up to 700 kbit/second
Communications protocol Bluetooth SPP
Environmental and safety specifi cations
Operating environment Indoors or in covered area outdoors, up to 2000 m altitude (for compliance to IEC61010 standard)
Storage temperature and humidity -20 °C to 50 °C, 80 % RH max, non-condensing
Operating temperature and humidity 0 °C to 40 °C, 80 % RH max, non-condensing
Maximum rated working voltage
Voltage terminals 1100 V rms
Voltage durability 5550 V rms ac for 1 minute, between voltage input terminals, voltage input terminals and current
probes, and voltage input terminals and case (50/60 Hz, 1 mA sense current)
Enclosure protection IP30 (per EN 60529)
Standards conformance
EMC EN 61326-1:1997+A1:1998 Class A
EN 61000-3-2:1995+A1:1998+A2:1998
EN 61000-3-3:1995
Safety E N 61010-1 2nd Edition; 2000
Voltage input unit: Contamination Level 2, Overvoltage Category 1000 V CAT III, 600 V CAT IV
(anticipated overvoltage: 8000 V)
Ordering information
Fluke 1750 Three-Phase Power
Recorder
Includes:
1750 acquisition unit
PDA wireless “front panel interface
and charger power plug adapters
4 - 400 A current probes (3140R)
5 test leads and clips
SD memory card
Fluke Power View and Fluke Power
Analyze software
Power cord with international plug set
Ethernet cable
Color localization set
Printed Getting Started manual
Product CD with software and users
manual PDF
Soft carrying case
Fluke offers a full suite of power qual-
ity test tools to locate, predict, prevent
and troubleshoot power problems.
Handheld troubleshooters for in-
stant analysis
Ready-to-use power loggers
Comprehensive power quality re-
corders
Power calibrators and standards
backed by Fluke metrology
expertise
The Fluke power quality set of
products offers the highest level of
performance and maintains the Fluke
promise of rugged and reliable test
tools.
Fluke Corporation
PO Box 9090, Everett, WA 98206 U.S.A.
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (425) 446-5116
In Europe/M-East/Africa +31 (0) 40 2675 200 or
Fax +31 (0) 40 2675 222
In Canada (800)-36-FLUKE or
Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com
©2006-2009 Fluke Corporation. Windows® is a
registered trademark of Microsoft Corporation.
Specifi cations subject to change without notice.
Printed in U.S.A. 10/2009 2428201F D-EN-N
Modification of this document is not permitted
without written permission from Fluke Corporation.
Pub-ID 11578-eng
Fluke. Keeping your world
up and running.®