DATASHEET - DS7-340SX024N0-N Soft starter, 24 A, 200 - 480 V AC, Us= 24 V AC/DC, Frame size FS2 Part no. Catalog No. Eaton Catalog No. EL-Nummer (Norway) DS7-340SX024N0-N 134913 DS7-340SX024N0-N 4134265 Delivery program Description With internal bypass contacts Function Soft starters for three-phase loads Mains supply voltage (50/60 Hz) ULN V AC 200 - 480 Supply voltage Us 24 V AC/DC Control voltage UC 24 V AC 24 V DC Assigned motor rating (Standard connection, In-Line) at 400 V, 50 Hz P kW 11 at 460 V, 60 Hz P HP 15 Ie A 24 Rated operational current AC-53 Rated operational voltage Ue 200 V 230 V 400 V 480 V Connection to SmartWire-DT no Frame size FS2 Technical data General Standards IEC/EN 60947-4-2 UL 508 CSA22.2-14 Approvals CE Approvals UL CSA C-Tick UkrSEPRO Climatic proofing Damp heat, constant, to IEC 60068-2-3 Damp heat, cyclic, to IEC 60068-2-10 Ambient temperature Operation C -5 - +40 up to 60 at 2% derating per Kelvin temperature rise Storage C -25 - +60 m 0 - 1000 m, above that 1 % derating per 100 m , up to 2000 m Altitude Mounting position Vertical Degree of protection Degree of Protection IP20 Protection against direct contact Finger- and back-of-hand proof Overvoltage category/pollution degree II/2 Shock resistance 8 g/11 ms Vibration resistance to EN 60721-3-2 2M2 Radio interference level (IEC/EN 55011) Static heat dissipation, non-current-dependent B Pvs Weight Main conducting paths W 1.1 kg 0.4 V AC 200 - 480 Rated operating voltage Ue 04/19/2019 Eaton 134913 ED2019 V55.0 EN 1/5 Supply frequency fLN Hz Rated operational current Ie A Ie A 24 at 230 V, 50 Hz P kW 5.5 at 400 V, 50 Hz P kW 11 at 200 V, 60 Hz P HP 7.5 at 230 V, 60 Hz P HP 7.5 at 460 V, 60 Hz P HP 15 AC-53 50/60 Assigned motor rating (Standard connection, In-Line) Overload cycle to IEC/EN 60947-4-2 AC-53a 24 A: AC-53a: 3 - 5: 75 - 10 Internal bypass contacts Short-circuit rating Type "1" coordination PKM0-25 (+ CL-PKZ0) Type 2" coordination (additional with the fuses for coordination type 1") 3 x 170M1365 Fuse base (number x part no.) 3 x 170H1007 Terminal capacities Cable lengths Solid mm 2 1 x (0.75 - 16) 2 x (0.75 - 10) Flexible with ferrule mm 2 1 x (0.75 - 16) 2 x (0.75 - 10) Stranded mm 2 1 x 16 Solid or stranded AWG 18 - 6 Tightening torque Nm 3.2 Screwdriver (PZ: Pozidriv) mm PZ2; 1 x 6 mm Control cables Solid mm 2 1 x (0.5 - 2.5) 2 x (0.5 - 1.0) Flexible with ferrule mm 2 1 x (0.5 - 1.5) 2 x (0.5 - 0.75) Stranded mm 2 1 x (0.5 - 1.5) 2 x (0.5 - 1.0) Solid or stranded AWG 1 x (21 - 14) 2 x (21 - 18) Tightening torque Nm 1.2 Screwdriver mm 0,6 x 3,5 DC-operated V DC 24 V DC +10 %/- 15 % AC operated V AC 24 V AC +10 %/- 15 % Control circuit Digital inputs Control voltage Current consumption 24 V mA External 24 V mA Pick-up voltage 1.6 x Us DC-operated V DC 17.3 - 27 AC operated V AC 17.3 - 27 DC operated V DC 0-3 AC operated V AC 0-3 DC operated ms 250 AC operated ms 250 ms 350 V 24 V AC/DC +10 %/- 15 % Drop-out voltage x Us Pick-up time Drop-out time DC operated Regulator supply Voltage 04/19/2019 Us Eaton 134913 ED2019 V55.0 EN 2/5 Current consumption Ie mA Notes 50 External supply voltage Relay outputs Number 2 (TOR, Ready) Voltage range V AC 250 AC-11 current range A 1 A, AC-11 Acceleration s 1 - 30 Deceleration s 0 - 30 Start voltage (= turn-off voltage) % 30 100 Start pedestal % 30 - 100 Soft start function Ramp times Fields of application Fields of application Soft starting of three-phase asynchronous motors 1-phase motors 3-phase motors Functions Fast switching (semiconductor contactor) - (minimum ramp time 1s) Soft start function Reversing starter External solution required Suppression of closing transients Suppression of DC components for motors Potential isolation between power and control sections Notes Rated impulse withstand voltage: * 1.2 s/50 s (rise time/fall time of the pulse to IEC/EN 609472 or 3) * Applies for control circuit/power section/enclosure Design verification as per IEC/EN 61439 Technical data for design verification Rated operational current for specified heat dissipation In A 24 Heat dissipation per pole, current-dependent Pvid W 0 Equipment heat dissipation, current-dependent Pvid W 1.1 Static heat dissipation, non-current-dependent Pvs W 1.1 Heat dissipation capacity Pdiss W 0 Operating ambient temperature min. C -5 Operating ambient temperature max. C 40 IEC/EN 61439 design verification 10.2 Strength of materials and parts 10.2.2 Corrosion resistance Meets the product standard's requirements. 10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements. 10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements. 10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects Meets the product standard's requirements. 10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements. 10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated. 10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated. 10.2.7 Inscriptions Meets the product standard's requirements. 10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated. 10.4 Clearances and creepage distances Meets the product standard's requirements. 10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated. 10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated. 10.7 Internal electrical circuits and connections Is the panel builder's responsibility. 10.8 Connections for external conductors Is the panel builder's responsibility. 10.9 Insulation properties 10.9.2 Power-frequency electric strength 04/19/2019 Is the panel builder's responsibility. Eaton 134913 ED2019 V55.0 EN 3/5 10.9.3 Impulse withstand voltage Is the panel builder's responsibility. 10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility. 10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. 10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be observed. 10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be observed. 10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. Technical data ETIM 7.0 Low-voltage industrial components (EG000017) / Soft starter (EC000640) Electric engineering, automation, process control engineering / Low-voltage switch technology / Load breakout, motor breakout / Semiconductor motor controller or soft starter (ecl@ss10.0.1-27-37-09-07 [ACO300011]) Rated operation current Ie at 40 C Tu A 24 Rated operating voltage Ue V 230 - 460 Rated power three-phase motor, inline, at 230 V kW 5.5 Rated power three-phase motor, inline, at 400 V kW 11 Rated power three-phase motor, inside delta, at 230 V kW 0 Rated power three-phase motor, inside delta, at 400 V kW 0 Function Single direction Internal bypass Yes With display No Torque control No Rated surrounding temperature without derating C 40 Rated control supply voltage Us at AC 50HZ V 24 - 24 Rated control supply voltage Us at AC 60HZ V 24 - 24 Rated control supply voltage Us at DC V 24 - 24 Voltage type for actuating AC/DC Integrated motor overload protection No Release class Other Degree of protection (IP) IP20 Degree of protection (NEMA) 1 Approvals Product Standards IEC/EN 60947-4-2; GB 14048.6; UL 508; CSA-C22.2 No 0-M91; CSA-C22.2 No 14-05 CE marking UL File No. E251034 CSA File No. 2511305 CSA Class No. 321106 Specially designed for North America No Suitable for Branch circuits Current Limiting Circuit-Breaker No Max. Voltage Rating 480 V Degree of Protection IP20; UL/CSA Type 1 04/19/2019 Eaton 134913 ED2019 V55.0 EN 4/5 Dimensions Additional product information (links) IL03902004Z Instructions for DS7 Soft Starter IL03902004Z Instructions for DS7 Soft Starter ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL03902004Z2018_05.pdf MN03901001Z Manual DS7 soft starters MN03901001Z Handbuch DS7 Sanftstarter Deutsch ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN03901001Z_DE.pdf MN03901001Z Manual DS7 soft starters English ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN03901001Z_EN.pdf MN03901001Z Manuale Softstarter DS7 italiano ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN03901001Z_IT.pdf CA04020001Z_EN-INT Product range catalog: Efficient Engineering for starting and controlling motors. http://www.eaton.eu/ecm/groups/public/@pub/@europe/@electrical/documents/content/pct_1095238.pdf 04/19/2019 Eaton Industries GmbH http://www.eaton.eu (c) 04/2019 by Eaton Industries GmbH Eaton 134913 ED2019 V55.0 EN 5/5